Model |
DR-120-12 |
DR-120-24 |
DR-120-48 |
|
DC Voltage: |
12V |
24V |
48V |
|
Rated Current: |
10A |
5A |
2.5A |
|
Current Range: |
0-10A |
0-5A |
0-2.5A |
|
Rated Power: |
120W |
120W |
120W |
|
Ripple & Noise (max.) Note.2: |
80mVp-p |
80mVp-p |
100mVp-p |
|
Voltage Adj. Range: |
12-14V |
24-28V |
48-53V |
|
Voltage Tolerance Note.3: |
±2% |
±1% |
±1% |
|
LINE REGULATION: |
±0.5% |
±0.5% |
±0.5% |
|
LOAD REGULATION: |
±1% |
±1% |
±1% |
|
Setup, Rise Time: |
500ms,70ms/230VAC 500ms,70ms/115VAC at full load |
|||
Hold Up Time: |
36ms/230VAC 32ms/115VAC at full load |
|||
Voltage Range: |
88~132VAC/176~264VAC selected by switch 248~370VDC |
|||
FREQUENCY RANGE: |
47~63Hz |
|||
AC Current: |
2.6A/115V 1.6A/230V |
|||
Efficiency: |
80% |
84% |
85% |
|
Inrush Current: |
COLD START 20A/115VAC 40A/230VAC |
|||
LEAKAGE CURRENT: |
<3.5mA / 240VAC |
|||
Over Load: |
105%~150% rated output power |
|||
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
||||
Over Voltage: |
15 ~ 16.5V |
29 ~ 33V |
58 ~ 65V |
|
Protection type : Shut down o/p voltage, re-power on to recover |
||||
OVER TEMPERATURE: |
85°C±5°C(TSW1) |
90°C±5°C(TSW1) |
90°C±5°C(TSW1) |
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
||||
Working Temp.,: |
-10°C~+60°C; (Refer to “Derating Curve”) |
|||
WORKING HUMIDITY: |
20 ~ 90% RH non-condensing |
|||
Storage Temp., Humidity: |
-20°C~+85°C; 10%~95%RH |
|||
Temp. Coefficient: |
±0.03%/°C(0~50°C) |
|||
Vibration: |
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
|||
Withstand Voltage: |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
|||
Isolation Resistanc: |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C / 70% RH |
|||
EMC EMISSION: |
Compliance to EN55032, EN55035 Class B, EN61000-3-2,-3 |
|||
DIMENSION: |
65.5*125*100 mm (W*H*D) |
其他信息
重量 | 1.5 kg |
---|---|
尺寸 | 15 × 20 × 15 cm |
Reviews